The EBS6R Residual Current Circuit Breaker (RCCB) is designed to provide optimal protection against electric shocks and fire hazards, making it an essential component in residential, tertiary sector, and industrial applications. This circuit breaker works seamlessly with EBS6B and EBS6BN miniature circuit breakers, ensuring reliable switching and isolation functions. It safeguards users from direct and indirect contact with electricity and is equipped with overload and short circuit protection features that enhance safety in various environments.

Specifications

Attribute Details
Model Name EBS6R
Standard IEC61008-1
Poles 2P, 4P
Rated Current In (A) 25, 32, 40, 50, 63
Rated Voltage Un (V) 230/400V AC 50/60Hz
Rated Residual Currents, I△n (mA) 10, 30, 100, 300
Rated Residual Non-Operating Current 0.5xl△n
Rated Impulse Withstand Voltage Uimp 6,000V
Rated Conditional Short-Circuit Current, Inc 6kA
Installation Installed on 35mm DIN rail
Ambient Temperature -5~+40℃ (average must not exceed +35℃ within 24h)
Altitude ≤2,000m
Relative Humidity ≤95%
Pollution Level II
Installation Location Mount in an area with no obvious vibration or impact

Additional Information

Product Advantages:

  • Enhanced safety features against electrical hazards.
  • Compatible with EBS6B and EBS6BN circuit breakers.
  • Robust design suitable for various installation environments.