KNLE1-100 Leakage Circuit Breaker
Inquire NowDescription
The KNLE1-100 Leakage Circuit Breaker is an essential safety device designed to provide leak protection for electrical systems. Suitable for single-phase lines up to 230V and three-phase lines up to 400V, it can handle rated currents of up to 100A. This circuit breaker is engineered to automatically disconnect power within 0.2 seconds in the event of an electric shock or when leakage current exceeds safe limits, ensuring maximum safety for both users and equipment.
In addition to leak protection, the KNLE1-100 also offers overload and short-circuit protection, making it a versatile solution for various electrical applications. It meets the GB16917.1 standards, ensuring reliability and compliance with regulatory requirements.
Specifications
Frame Class | 100A |
---|---|
Rated Working Voltage | 240/415V |
Rated Frequency | 50/60Hz |
Rated Working Current | 63, 80, 100A |
Rated Residual Operating Current | 0.03, 0.1A |
Rated Residual Un-Operating Current | 0.015, 0.05A |
Sensibility | AC Type |
Maximum Operating Time | I△n t ≤ 0.3s, 5I△n t ≤ 0.04s |
Instant Release Type | B, C, D |
Limiting Value of Un-Operating Current | 6In |
Rated Limiting Short-Circuit Current | 6000A |
Pole Number | 1P+N, 2P, 3P, 3P+N |
Mechanical Life | 8000 cycles |
Electric Life | 4000 cycles |
Additional Information
Sequence No. | Release | Test Current I/In | Start State | Tripping Time | Expected Result |
---|---|---|---|---|---|
1 | C | 1.13In | Cold state | t≤2h | Not tripping |
2 | C | 1.45In | Start right after the serial NO. 1 test | t<2h | Tripping |
3 | C | 2.55In | Cold state | 1sTripping |
|
4 | C | 5In | Cold state | t≤0.1s | Not Tripping |
5 | C | 10In | Cold state | t<0.1s | Tripping |