KNLE1-32 Leakage Circuit Breaker

Inquire Now

Description

The KNLE1-32 Leakage Circuit Breaker is designed to provide reliable leak protection for electrical systems. This device is suitable for single-phase lines up to 230V and three-phase lines up to 400V, with a rated current capacity of up to 32A. In the event of an electrical shock or if the leak current exceeds the specified limit, the breaker acts swiftly, automatically disconnecting power within just 0.2 seconds to safeguard both individuals and equipment.

In addition to leak protection, the KNLE1-32 also offers overload and short-circuit protection, ensuring comprehensive safety. It performs well under normal conditions, adhering to GB16917.1 standards, making it a reliable choice for various applications.

Specifications

Frame Class 32A
Rated Working Voltage 240/415V
Rated Frequency 50/60Hz
Rated Working Current 6, 10, 16, 20, 25, 32A
Rated Residual Operating Current 0.03A
Rated Residual Un-operating Current 0.015A
Sensitivity AC Type
Maximum Operating Time IΔn t≤0.1s, 5IΔn t≤0.04s
Instant Release Type B, C, D
Limiting Value of Un-operating Current 6In
Rated Limiting Short-Circuit Current 4500A
Pole Number 1P+N, 2P, 3P, 3P+N, 4P
Mechanical Life 8000
Electric Life 4000

Additional Information

Sequence NO Release Test Current I/In Start State Tripping Time Expected Result
1 C 1.13In Cold state t≤1h Not tripping
2 C 1.45In Start right after the serial NO. 1 test t<1h Tripping
3 C 2.55In Cold state 1s<t<60s Tripping
4 C 5In Cold state t≤0.1s Not Tripping
5 C 10In Cold state t<0.1s Tripping