KEYPOWER Resistive Load Bank 500 kw for generator test

Inquire Now

Description

The KEYPOWER Resistive Load Bank is a high-performance testing device designed specifically for generator load testing. With a robust capacity of 500 kW, this load bank allows for accurate and reliable performance assessments of generators, UPS systems, and battery banks. Engineered through independent research and development, it features premium components ensuring durability and reliability, making it easy to transport and set up for various testing scenarios.

This load bank simulates realistic load conditions, providing essential data for operational efficiency and safety. It is perfect for conducting thorough load tests, guaranteeing that your power systems operate at their best under load.

Specifications

Measurement Range Accuracy Resolution Overload
Voltage (V) 10.0~500.0V ± (0.4% reading + 0.1% range) 0.1V 600V
Current (A) 0.030~5.000A ± (0.4% reading + 0.1% range) 0.001A 6A
Power Factor 0.20~1.00 ±0.02 0.001
Frequency 45~65Hz ±0.2Hz 0.01Hz
Running Time 99h59m ±2min/hour 1 minute
Energy (kWh) 99999kWh ± (0.4% reading + 0.1% range) 0.001kWh

Additional Information

This load bank features:

  • Resistive type of load with a power factor of 1.0, utilizing high-grade materials for durability.
  • Rated testing voltage of AC 3P4W, 110-480V at 50/60 Hz.
  • Forced air-cooling system with fans for efficient operation.
  • Multiple control modes including local manual and optional remote control.
  • Comprehensive parameter display via a multifunction electricity meter.
  • Designed for use in environments with ambient temperatures ranging from -10 to +50 °C.

Product Inquiry Form