CQB2-63 6kA Miniature Circuit Breaker

Inquire Now

Single phase and three phase applications
·High Interruption rating capabilities.
·Overload protection
·Short circuit protection
·Positive isolation
Suitable for industrial, commercial, high-rise and civil residences circuit protection.

1 Overview and applications

·Single phase and three phase applications

·High Interruption rating capabilities.

·Overload protection

·Short circuit protection

·Positive isolation

Suitable for industrial, commercial, high-rise and civil residences circuit protection.

2 Type designation

Sinoart enterprise content manager system | Sinoart CMS

3 Technical data

Specifications

Rated insulation voltage

500V

Rated impulse withstand voltage Uimp

4000V

Rated current(A)

6A、10A、16A、20A、25A、32A、40A、50A、63A

Rated frequency

50Hz / 60Hz

Number of poles

1P 、1P+N、2P 、3P 、3P+N、4P

Rated breaking capacity Icn=Ics(A)

6000A

Mechanical life(cycles)

≥10000

Electrical life(cycles)

≥6000

Tripping characteristics

B 、 C 、 D

Grid distance

45mm

Protection degree

IP20

Standard

IEC60898 -1、GB/T10963.1

Compliant certification

CCC

Table 1 Tripping characteristics(Reference temperature 30℃)

Test Curve Test current ln(A) Status Time limit for tripping or non-tripping Expected result Remark
a B、C、D 1.13ln Cold t≤1h Non-tripping Current smoothly rises to specified value within 5s
b B、C、D 1.45ln Following item a test t<1h Tripping
c B、C、D 2.55ln Cold 1s<t<60s(ln≤32A)
1s<t<120s(ln>32A)
Tripping
d B
C
D
3ln
5ln
10ln
Cold t≤0.1s Non-tripping Switch on the power supply by closing the auxiliary switch
e B
C
D
5ln
10ln
20ln
Cold t<0.1s Tripping Switch on the power supply by closing the auxiliary switch

Note: The term “cold ” means that the test is carried out at a reference calibration temperature without load before the test.

4 Order Specifications

Sinoart enterprise content manager system | Sinoart CMS

5 Dimensions(unit :mm)

Sinoart enterprise content manager system | Sinoart CMS

Sinoart enterprise content manager system | Sinoart CMS

6 Conductor requirements and cross-sectional area

Copper cross-sectional area(mm2) Rated current In(A)
1 In≤6
1.5 6<In≤13
2.5 13<In≤20
4 20<In≤25
6 25<In≤32
10 32<In≤50
16 50<In≤63

Product Inquiry Form