CQB2HL-63 10kA Residual Current Operated Circuit Breaker with Over-current Protection (Electronic)

Inquire Now

Description

The CQB2HL-63 10kA Residual Current Operated Circuit Breaker with Over-current Protection is designed for enhanced circuit protection in industrial, commercial, high-rise, and residential installations. This essential device offers overload and short circuit protection, ensuring safety and reliability in electrical systems. It features adjustable tripping curves (B, C, D) and is engineered to protect individuals from indirect contacts while providing additional safeguards against direct contacts. Moreover, it serves to mitigate the fire hazards associated with insulation faults, conforming to the stringent IEC 61009-1 standards.

Specifications

Specification Details
Rated voltage (V) 230V~(1P+N, 2P), 400V~(3P/3P+N/4P)
Rated current (A) 6, 10, 16, 20, 25, 32, 40, 50, 63
Rated tripping current I△n(mA) 30, 50, 75, 100, 300
Poles 1P+N, 2P, 3P, 3P+N, 4P
Rated breaking capacity lcn(A) 10000
Mechanical & Electrical life Mechanical ≥20000, Electrical ≥6000
Tightening torque (N.m) 3.5
Pollution degree 2
Protection class IP20
Overvoltage category Ⅱ, Ⅲ
Tripping characteristics 2

Additional Information

Nominal operation conditions:

  • Ambient temperature range: -5℃ to +40℃, average temperature in 24 hours not exceeding +35℃
  • Altitude: ≤ 2000m
  • Relative humidity: Not exceeding 50% at maximum temperature of +40℃; higher humidity is permissible at lower temperatures, e.g., RH can be 90% at +20℃
  • Mounting type: Din rail embedded (TH35-7.5)
  • Installation conditions: The circuit breaker should be mounted vertically, away from significant impacts and vibrations, with the outer magnetic field not exceeding five times the Earth’s magnetic field.

Tripping Characteristics

Item Type Rated current ln(A) Initial status Time limit for tripping or non-tripping Expected result Remarks
a B, C, D 1.13ln Cold t ≤ 1h Non-tripping Current smoothly rises to specified value within 5s
b B, C, D 1.45ln Following previous test t < 1h Tripping
c B, C, D 2.55ln Cold 1s < t < 60s (ln ≤ 32A)
1s < t < 120s (ln > 32A)
Tripping

Conductor Requirements and Cross-Sectional Area

Copper cross-section (mm²) Rated current In(A)
1 In ≤ 6
1.5 6 < In ≤ 13
2.5 13 < In ≤ 20
4 20 < In ≤ 25
6 25 < In ≤ 32
10 32 < In ≤ 50
16 50 < In ≤ 63