Description
The ZF16-252(L)/Y4000-50 Gas Insulated Metal-Enclosed Switchgear (GIS) is engineered for advanced electrical systems, adept at handling three-phase AC power at a frequency of 50Hz and a rated voltage of 252kV. This robust unit complies with national standards (GB7674-2008) and international standards (IEC60517), ensuring reliability and safety in operation. Its design features a common enclosure for the three-phase main busbars, while all other components are compartmentalized for enhanced performance and protection against environmental factors.
Specifications
| Attribute | Details |
|---|---|
| Rated Voltage | 252 kV |
| Frequency | 50 Hz |
| Installation Site | Indoor or Outdoor |
| Ambient Temperature | -25℃~+40℃ (for circuit breaker) / -40℃~+40℃ (for other parts) |
| Altitude | 1000 m (No limitation for special order) |
| Humidity |
Relative humidity at average per day (25℃): ≤95% Relative humidity at average per month: ≤90% |
| Wind Speed | ≤34 m/s (wind pressure ≤700Pa) |
| Icing Thickness | 20 mm |
| Seismic Intensity |
Horizontal acceleration: ≤0.3g Vertical acceleration: ≤0.15g |
| Creepage Distance | 25 mm/kV (pollution class III), 31 mm/kV (class IV) |
Additional Information
- Ensure the breaker is located away from combustible, explosive, corrosive materials, and areas with violent vibrations.