CEZC100-250 SHT UVR UVRN

Inquire Now

With 30 years experience, we produce quality product with moderate price. Looking for dealer, wholesaler and other type of clients for further cooperation.

Remote tripping

Shunt Trip (SHT) or Under Voltage Release (UVR/UVRN).

Shunt Trip (SHT)

·This release trips the circuit breaker when the control voltage rises above 0.7 x Un
·Control signals can be of the impulse type (u 20 ms) or maintained.

Under Voltage Release (UVR/UVRN)

  • This release trips the circuit breaker when the control voltage drops below a tripping threshold

  • Tripping threshold between 0.35 and 0.7 times the rated voltage

  • Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated voltage.

Operation

When the circuit breaker has been tripped by an SHT or UVR/UVRN release, it must be reset locally:

  • SHT or UVR/UVRN tripping takes priority over manual closing

  • in the presence of a standing trip order, closing of the contacts, even temporary, is not possible.

Circuit breaker tripping by an SHT/UVR/UVRN release meets the requirements of standard IEC 60947-2.

Product Inquiry Form