TRMF2 125A 2 POLES, Compact Size, LS Design MCCB

Inquire Now

TRM series circuit breaker and auxiliaries comply with the following international standard:
1.IEC/EN 60947-1
Low-voltage switchgear and controlgear-part 1: General rules;
2.IEC/EN 60947-2
Low-voltage switchgear and controlgear-part 2: Circuit breakers;
TRM series MCCB(Standard use environment for TRM series MCCB)
1. Ambient temperature: Within the range of -5oC–+55oC(However, when the temperature exceed 40oC,it should be considered to reduce the capacity to use);
2. Relative humidity: Within the range of 45%–85%;
3. Altitude: 2000m or less(However, if it exceeds 1000m, atmosphere correction through humidity test and withstand voltage test can be considered);
4. Atmosphere where excessive steam, oil steam, smoke, dust, salt and other corrosive materials do not exist;
Classification:
According to the poles: 1-pole, 2-poles, 3-poles, 4-poles
According to the breaking capacity: S-type, H-type
According to the rated current: Fix type, Adjustable type(08In-1.0In)

TRM series MCCB

Standard:
TRM series circuit breaker and auxiliaries comply with the following international standard:
1.IEC/EN 60947-1
Low-voltage switchgear and controlgear-part 1: General rules;
2.IEC/EN 60947-2
Low-voltage switchgear and controlgear-part 2: Circuit breakers;

TRM series MCCB(Standard use environment for TRM series MCCB)
1. Ambient temperature: Within the range of -5oC–+55oC(However, when the temperature exceed 40oC,it should be considered to reduce the capacity to use);
2. Relative humidity: Within the range of 45%–85%;
3. Altitude: 2000m or less(However, if it exceeds 1000m, atmosphere correction through humidity test and withstand voltage test can be considered);
4. Atmosphere where excessive steam, oil steam, smoke, dust, salt and other corrosive materials do not exist;

Classification:
According to the poles: 1-pole, 2-poles, 3-poles, 4-poles
According to the breaking capacity: S-type, H-type
According to the rated current: Fix type, Adjustable type(08In-1.0In)


Technical data table:

Ampere frame size TRMF2(125A)
Breaking capacity code S H
Product code and poles 1P 2P 3P 4P 1P 2P 3P 4P
TRMF2-S1 TRMF2-S2 TRMF2-S3 TRMF2-S4 TRMF2-H1 TRMF2-H2 TRMF2-H3 TRMF2-H4
Rated current, In(A) 15, 20, 30, 40, 50, 60, 75, 80, 100, 125
Adjustable part Rated current setting(0.8In-1.0In) χ χ
Lockup device for operating handle χ χ
Rated operational voltage, Ue(V), AC 50/60 Hz 240/415
Rated insulation voltage, Ui(V) 1000
Rated impulse withstand voltage, Uimp(kV) 8
Standard Conformity with IEC/EN 60947-2
Rated frequency(Hz) 50/60
Rated short-circuit breaking capacity, Icu(kA)
AC 240V 18 35 25 50
415V 18 35
Ics=% * Icu 50% 100% 50% 100%
Mechanical life(circle) 8500
Electrical life(circle) 1500
Dimension:
Length*Width*Height
1-pole 130*25*60
2-poles 130*50*60
3-poles 130*75*60
4-poles 130*100*60