12V 65AH~250AH Maintenance Free VRLA Lead Acid Battery for UPS Backup

Inquire Now

1.Using oxygen recombination technology: maintenance-free;
2.PbCaSn alloy for plate grids: less gassing, less self-discharging;
3.High quality AGM separator: extend cycle life and prevent micro short circuit;
4.ABS material: increase the strength of battery container. (Flame-retardant ABS is optional);
5.High purity raw material: ensure low self discharge rate;
6.Silver-coated copper terminals (T1, T2 terminal), brass terminals and lead terminals improve the electric conductivity

>About VRLA battery (AGM & GEL)

What is VRLA battery?

VRLA(Valve Regulated Lead Acid) battery is sealed lead -acid battery. liclides GEL type and AGM type, both have the following characteristics:

*is sealed using special pressure valves and should never be opened.

*is completely maintenance-free,needn’t topping in service life.

*all of its electrolyte are immobilized (absorbed in AGM or fixed in Gel structure).

*uses recombination reaction to prevent the escape of hydrogen and oxygen gases which normally lost in flooded lead- acid battery.

*is non-spillable, and therefore can be operated in virtually any position(except upside down).

What is GEL battery?

Besides the characteristics of VRL A, GEL battery has :

*using thixotropic gelled electrolyte, it is in a solid state between the plates and separators.

*not like traditional AGM electrolyte “starve” design, GEL battery has more 15~25%electrolyte volume than AGM type.

*different type of separator, such as PE, PVC etc .

Differences between GEL batteries and absorbed glass mat(AGM) batteries?

*Both are sealed recombinant batteries. Both are sealed valve-regulated lead-acid (VRLA).

AGM batteries and GEL batteries are both considered “acid-starved” and the electrolyte does not flow like a normal liquid.

*The gel electrolyte has the consistency and appearance of petroleum jelly. Like gelled electrolyte batteries,

AGM batteries are also considered non-spillable – all of the liquid electrolyte is trapped in the sponge-like matted glass fiber separator material.

*Due to the physical properties of the gelled electrolyte, gel battery has higher internal resistance. Thus AGM batteries has excellent

performance for high current/power discharge and GEL excels in high/lower temperature stability and lower current/power discharge applications.

*AGM batteries has higher specific energy density than GEL batteries. But GEL batteries has longer service life.

What is the difference between VRLA batteries and traditional wet/flooded batteries?

*Wet batteries do not have special pressurized sealing vents, as they do not work on the recombination principle(gases escaped inside the battery during charging).

*It contains liquid electrolyte that can spill/flow and cause corrosion if tipped or punctured. Therefore, they are not air transportable without special containers.

*It can only be installed “upright” and “acid protection” must be maintained at the same time.

*As the wet batteries will lose gases during charging ,it is need maintenance(topping) periodically.

*As the electrolyte can flow , “stratification” will occur and need more overcharge to mix.

>Applications

1.Solar and wind energy storage system

2.EPS and UPS battery backup

3.Signal system , emergency lighting system , security system

4.Telecommunication Equipment

5.Power source for portable devices or tools

>Main Features

1.Using oxygen recombination technology: maintenance-free;

2.PbCaSn alloy for plate grids: less gassing, less self-discharging;

3.High quality AGM separator: extend cycle life and prevent micro short circuit;

4.ABS material: increase the strength of battery container. (Flame-retardant ABS is optional);

5.High purity raw material: ensure low self discharge rate;

6.Silver-coated copper terminals (T1, T2 terminal), brass insert terminals and lead terminals improve the electric conductivity

>Specification

Battery Model No. FBR12V65Ah
Nominal Voltage 12V
Capacity
(25oC)
20HR(5.25V) 65Ah
10HR(5.25V) 57Ah
1HR(4.80V) 40Ah
Dimension Length 350±2mm
Width 167±2mm
Height 175±2mm
Total height 175±2mm
Approx. Weight 20kg±4%
Terminal type F14
Internal resistance
(Fully charged,25oC)
Approx 6mΩ
Capacity affected by
temperature(20HR)
40oC 102%
25oC 100%
0oC 85%
-15oC 65%
Self-discharge
(25oC)
3month Remaining Capacity:91%
6month Remaining Capacity:82%
12month Remaining Capacity:65%
Nominal operating temperature 25oC±3oC(77oF±5oF)
Operating
temperature range
Discharge -15oC-50oC(5oF-122oF)
Charge -10oC-50oC(14oF-122oF)
Storage -20oC-50oC(-4oF-122oF)
Float charging voltage
(25oC)
13.5 to 13.8V
Temperature compensation:-18mV/oC
Cyclic charging voltage
(25oC)
14.5 to 15V
Temperature compensation:-30mV/oC
Max charging current 19.5A
Max discharging current 650A(5sec.)
Designed floating life(20oC) 10years

>Structure and composition

Component Pos. plate Neg. plate Container Cover Separator Electrolyte Safety valve Terminal
Raw material Lead dioxide Lead ABS ABS AGM Sulfuric acid Rubber Copper


>Constant Current Discharge Characteristics(A,25oC)

F.V/Time 10min 15min 30min 60min 2h 3h 4h 5h 8h 10h 20h
9.6V 327 252 151 92.7 54.8 39.0 31.5 26.9 18.5 15.3 8.09
9.9V 317 246 148 91.3 54.5 38.8 31.3 26.8 18.4 15.2 8.08
10.2V 304 237 143 89.0 54.0 38.5 31.1 26.6 18.3 15.2 8.05
10.5V 291 229 140 87.1 53.2 38.3 30.9 26.4 18.2 15.1 8.01
10.8V 275 217 135 84.4 51.8 37.1 30.0 25.6 17.6 15.0 7.95

>Constant Power Discharge Characteristics(Watt,25oC)

F.V/Time 10min 15min 30min 60min 2h 3h 4h 5h 8h 10h 20h
9.60V 3532 2767 1691 1057 635 459 371 318 220 182 97.1
9.90V 3426 2701 1658 1041 631 456 368 316 219 182 96.9
10.2V 3284 2601 1607 1015 625 453 366 314 217 181 96.6
10.5V 3143 2512 1568 993 616 450 363 312 216 180 96.1
10.8V 2967 2380 1510 963 600 436 352 303 209 179 95.4