150-800kVA Data Center M25 Series Online Modular UPS Power Supply
Inquire Now
1.Hot-swappable design
2.N+X parallel redundancy system,
3.Intelligent fan control and redundant design
4.RS232/RS485/LAN/dry contact communication port
5.SNMP adapter(optional)
6.Fully DSP control and high reliability and performance
7.Allow 100% unbalanced load
8.7 inches touchable LCD screen
9.Manual maintenance bypass switch
3RW 120-800K
Main feature
1.Hot-swappable design
2.N+X parallel redundancy system,
3.Intelligent fan control and redundant design
4.RS232/RS485/LAN/dry contact communication port
5.SNMP adapter(optional)
6.Fully DSP control and high reliability and performance
7.Allow 100% unbalanced load
8.7 inches touchable LCD screen
9.Manual maintenance bypass switch
Application
1.IDC
2.Telecom system
3.IT room
4.Financial center
5.Precision instrument
6.Commercial facility
Specification
Model |
3RW120/150/180K |
3RW200/250/300K |
3RW400/500/600K |
3RW-300K |
3RW-500K |
3RW-600K |
3RW-800K |
||||||
Capacity |
120/150/180KVA |
200/250/300KVA |
400/500/600KVA |
300KVA |
500KVA |
600KVA |
800KVA |
||||||
Type of power module |
M20/M25/M30 |
M50 |
|||||||||||
Input mode |
3 Phase 4 Wires+ Ground |
||||||||||||
Input voltage(Vac) |
380V/220V±20%、400V/230V±20%、415V/240V±20% |
||||||||||||
Input Frequency(HZ) |
50Hz±10%、60Hz±10% |
||||||||||||
Input PF |
≥0.99 |
||||||||||||
Battery voltage(Vdc) |
±384 |
±240 |
|||||||||||
Battery quantity(Pcs) |
64 can’t be adjusted |
30-34 can be adjusted |
|||||||||||
UPS Power Factor |
1.0/0.9/0.8 |
0.9/1.0 |
|||||||||||
Output Voltage(Vac) |
380/220V、400/230V、415/240V |
||||||||||||
Output Frequency(HZ) |
50Hz±4%;Mains overrun or battery mode output is 50Hz±0.2% 60Hz±4%;Mains overrun or battery mode output is 60Hz±0.2% |
||||||||||||
Output voltage Stability |
±1%(Static);±2%(Load change from 0 ~ 100% )
|
||||||||||||
Efficiency (AC mode @ full loads) |
≥94% |
≥96.5% |
|||||||||||
Output voltage recovery time |
<20ms(Load change from 0 – 100% ) |
||||||||||||
Overload |
Rated Load 125% ,runs 10min |
||||||||||||
Communication function |
RS232/RS485/422/ dry contact/TCP/IP Expansion cards |
||||||||||||
SMMP(optional) |
Can be network monitored by SNMP adapter |
||||||||||||
Parallel function |
Yes(for optional) |
||||||||||||
Storage Environment Temperature |
-25℃~60℃ |
||||||||||||
Working Environment Temperature |
-5℃~40℃ |
||||||||||||
IP Class |
IP31 |
||||||||||||
Cooling |
Speed controlled air cooling |
||||||||||||
Noise(dB) |
≤55dB(Within 1 meter) |
||||||||||||
Structure |
19 inches Standard |
||||||||||||
Monitor Management System |
UPSupervisor |
||||||||||||
Display |
Touchable screen LCD/LED |
||||||||||||
Dimension(W*D*H) |
600*800*1600 |
800*800*2000 |
2000*800*2000 |
800*800*2000 |
1400*800*2000 |
1400*800*2000 |
2000*800*2000 |
||||||
Weight (Kg) |
180KG |
250KG |
450KG |
250KG |
400KG |
500KG |
540KG |
Note:
1, Because the products are continuously improved, please contact the company or dealer to inquiry the latest specification.