Copper Conductor XLPE Insulated 2X6mm2 0.6/1kV XS ABC Aerial Bundled Cable
Inquire NowAerial Bundled Cable is designed for residential and rural areas for reducing the bushfire Aerial Bundled Cable is designed for residential and rural areas for reducing the bushfire hazards.?The XLPE covering contains a high level of carbon black for UV resistance. It is designed for where reliability, safety and low installation cost are required, but it is only for short spans due to increased weight.
ABC CABLE XS 2X6 MM2BLACK
Application
Aerial Bundled Cable is designed for residential and rural areas for reducing the bushfire Aerial Bundled Cable is designed for residential and rural areas for reducing the bushfire hazards. The XLPE covering contains a high level of carbon black for UV resistance. It is designed for where reliability, safety and low installation cost are required, but it is only for short spans due to increased weight.
Dimenison Characteristics:
Pos. | Description | Unit | Data |
1 | GENERAL DESIGN AND FEATURES | ||
1.1 | Rated Voltage U0/U (Um) | kV | 0.6/1 |
1.2 | Maximum Admissible current on air @ 40°C | A | 55 |
1.3 | Number of conductors (including neutral) | # | 7 |
1.4 | Cable schematic cross section | – | Please attach drawing |
1.5 | Cable weight | Kg/km | 147 |
1.6 | Minimum bending radius | mm | 220 |
1.7 | Minimum pullig force | N | 1200 |
1.8 | Maximum bundlediameter | mm | 12 |
1.9 | Maximum operating temperature (insulation) Normal operation/ Short Circuit (5s duration) | °C | 90/250 |
1.10 | Provision of Type test reports | Y/N | Please attach reports |
2 | CORES | ||
2.1 | Marking | – | Please attach description and layout (for Phases and Neutral) |
2.2 | Outer diameter | mm | 5.9 |
2.3 | Assembly of cores | ||
2.3.1 | Lay type ( helically) | Y/N | Y |
2.3.2 | Lay direction | – | Right |
2.3.3 | Maximum length of lay | mm | 300 |
3 | PHASE CONDUCTOR | ||
3.1 | Material (detailed description) | – | Copper |
3.2 | Shape and compaction | – | Circular Compact |
3.3 | Cross sectional area | mm2 | 6 |
3.4 | Class (IEC 60228) | # | 2 |
3.5 | Number of wires | # | 7 |
3.6 | Stranding lay direction | – | Left |
3.7 | Conductor diameter | mm | 3.3 |
3.8 | Lay length (outer layer) | mm | 66 |
3.9 | Breaking force | DaN | 1200 |
3.10 | Conductor resistance | Ω/km | 3.08 |
4 | NEUTRAL CONDUCTOR (FILL IN JUST IF DIFFERENT FROM PHASE) | ||
4.1 | Material (detailed description) | – | Copper |
4.2 | Shape and compaction | – | Circular Compact |
4.3 | Cross sectional area | mm2 | 6 |
4.4 | Class (IEC 60228) | 2 | |
4.5 | Number of wires | # | 7 |
4.6 | Stranding lay direction | – | Left |
4.7 | Conductor diameter | mm | 3.3 |
4.8 | Lay length (outer layer) | mm | 66 |
4.9 | Breaking force | DaN | 1200 |
4.10 | Conductor resistance | Ω/km | 3.08 |
5 | INSULATION | ||
5.1 | Material (detailed description) | – | XLPE |
5.2 | Colour | – | BLACK |
5.3 | Thickness | ||
5.3.1 | Nominal value | mm | 1.2 |
5.3.2 | Mean value | mm | ≥1.2 |
5.3.3 | Minimum value | mm | ≥0.98 |
6 | DRUMS | ||
6.1 | Material | – | Iron wooden drum (1100*1100*1100) |
6.2 | Weight | kg | 70 |
6.3 | Cable length per drum | m | 4000 |