CQB2-125 10kA Miniature Circuit Breaker
Inquire Now
Single phase and three phase applications
·High breaking capacity up to 10KA
·Overload protection
·Short circuit protection
·Positive isolation
Suitable for industrial, commercial, high-rise and civil residences circuit protection.
1 Application
·Single phase and three phase applications
·High breaking capacity up to 10KA
·Overload protection
·Short circuit protection
·Positive isolation
Suitable for industrial, commercial, high-rise and civil residences circuit protection.
2 Type designation
3 Technical data
Specifications | |
Rated voltage(V) |
AC230V、AC400V |
Nominal current (A) |
63A、80A、100A、125A |
Number of poles |
1P 、2P 、3P 、4P |
Tripping curves | C、D |
Rated short-circuit breaking capacity lcu(A) |
10000A |
Rated service Short-circuit breaking capacity Ics(A) |
7500A |
Rated impulse withstand voltage Uimp(V) |
4000V |
Mechanical life(cycles) |
≥8000 |
Electrical life(cycles) |
≥1500 |
Tripping characteristics |
table 2 |
Protection degree |
IP20 |
Standards |
IEC60947-2、GB/T14048.2 |
Compliant certification |
CCC |
Table2 Tripping characteristics(Reference temp.30℃)
Item | Curve | Test current ln(A) | Initial status | Time limit for tripping or non-tripping | Expected result | Remark |
a | C、D | 1.05ln | Cold | 1h(ln≤63A) 2h(ln>63A) |
Non-tripping | Current smoothly rises to specified value within 5s |
b | C、D | 1.3ln | Following Item a test | 1h(ln≤63A) 2h(ln>63A) |
Tripping | |
c | C、D | 2ln | Cold | 1s<t<300s | Tripping | |
d | C D |
8ln×80% 12ln×80% |
Cold | t≤0.2s | Non-tripping | Switch on the power supply by closing the auxiliary switch |
e | C D |
8ln×120% 12ln×120% |
Cold | t<0.1s | Tripping | Switch on the power supply by closing the auxiliary switch |
Note: The terminology “Cold ” means that the test is performed at the base calibration temperature with no load prior to the test.
4 Order Specifications
5 cross-sectional area
Rated current Ie Copper cross-sectional area (mm2) | |
50A<in≤63a< td=”” style=”box-sizing: border-box”> | 16 |
63A<in≤80a< td=”” style=”box-sizing: border-box”> | 25 |
80A<in≤100a< td=”” style=”box-sizing: border-box”> | 35 |
100A<in≤125a< td=”” style=”box-sizing: border-box”> | 50 |
6 Order Specifications
When ordering circuit breakers, the following points should be specified:
A) Product models, such as CQB2-125;
B) Poles of circuit breakers, such as 1P, 2P, 3P, 4P;
C) Types of instantaneous tripping, such as type C and D;
D) Rated current of circuit breakers, such as 63A, 80A, 100A, 125A;
E) Order quantity, e.g. 100 pcs
Purchase order template
CQB2-125 2P C/100A 100pcs
7 Dimensions(unit :mm)