CQB5aL-63 4.5kA Residual Current Operated Circuit Breaker with Over-current Protection

Inquire Now

·Overload protection
·Short circuit protection
·Protect people against indirect contacts and additional protection against direct contacts.
·Protect installations against fire hazard due to insulation faults.
·High-quality residual current device
·Wide variety of rated tripping currents
Suitable for industrial, commercial, high-rise and civil residences circuit protection.

1 Overview and applications

·Overload protection

·Short circuit protection

·Protect people against indirect contacts and additional protection against direct contacts.

·Protect installations against fire hazard due to insulation faults.

·High-quality residual current device

·Wide variety of rated tripping currents

Suitable for industrial, commercial, high-rise and civil residences circuit protection.

2. Type designation

Sinoart enterprise content manager system | Sinoart CMS

3 Technical data

Specifications
Rated voltage (V) : 230V~/400~
Rated current (A) 10、16、20、25、32、40、50、63
Rated sensitivity lrn (mA) 30、50、100
Rated residual non-operating current 0.5 lrn
Poles 1P+N、2P、3P+N、4P
Rated breaking capacity lcu(A) 4500
Rated residual making and breaking capacity lr m 2000A
Tripping characteristic Table 2
Mechanical &Electrical life Mechanical ≥ 4000 ;Electrical≥ 2000
Pollution degree 2
Protection class IP20
Overvoltage category
Standards IEC61009-1、GB/T16917.1
Compliant certification CCC

Table 2 Tripping characteristics

Rated current(A) Test current Initial status Tripping time Expected result Remarks
≤63 1.13In Cold t≤1h Non-tripping
≤63 1.45In Following previous test t<1h tripping Current smoothly rises to specified value in 5s
≤63 2.55In Cold 1s<t<60s(In≤32A)
1s<t<120s(In>32A)
tripping
≤63 3In Cold t≤0.1s Non-tripping B
5In t<0.1s tripping
5In t≤0.1s Non-tripping C
10In t<0.1s tripping
10In t≤0.1s Non-tripping D
20In t<0.1s tripping

Note: The status “cold ” means that the test is carried out at a reference calibration temperature without load before the test.

4 Order Specifications
·When ordering circuit breakers, the following points should be specified:

A) Product models, such as CQB5aL-63;

B) Poles of circuit breakers, such as (1P+N);

C) Rated current of circuit breakers, such as 16A、20A、25A;

D) Rated residual operating current, such as 30mA;

E) Order quantity, such as 100 pcs

·Purchase order template

CQB5aL-63 1P+N C/16A 30mA 100pcs

5 Conductor requirements and cross-sectional area

Rated current (A) Nominal cross-sectional area(mm2)
≤10 1.5
16~20 2.5
25 4
32 6
40~50 10
63 16

6.Dimensions and installation sizes (mm)