CQB7R-125 10kA Miniature Circuit Breaker Reclosing

Inquire Now

CQB7R-125 Reclosing MCB is used to combine with Prepaid Meter, when the electricity user prepaid is used up, the MCB will break automatically when getting a signal from the Prepaid Meter. It can be switched on automatically when the Prepaid Meter get a signal that user have bought the electricity.

1 Application

CQB7R-125 Reclosing MCB is used to combine with Prepaid Meter, when the electricity user prepaid is used up, the MCB will break automatically when getting a signal from the Prepaid Meter. It can be switched on automatically when the Prepaid Meter get a signal that user have bought the electricity.

2 Type designation

3 Technical data

Specifications
Rated voltage 230V~(1P+N,2P)、400V~(3P,3P+N,4P)
Rated impulse withstand voltage Uimp 6000V
Rated current(A) 40、50、63、80、100、125
Rated frequency 50Hz / 60Hz
Number of poles 1P+N、2P、3P、3P+N、4P
Rated breaking capacity lcn(A) 6kA, 10kA(High breaking type)
Short-circuit capacity Ics(A) 6kA, 7 .5kA(High breaking type)
Mechanical life(cycles) ≥10000
Electrical life(cycles) ≥6000
Overvoltage category
Torque 2.5N·M
Automatic closing time t ≤ 3s
Automatic switch-off time t≤ 2s
Signal Connection Wire Length 300mm (Customizable on demand)
Tripping characteristics See Table 1
Pollution degree 2
Standard IEC60898-1、GB10963.1
Compliant certification CCC


Table 1 Tripping characteristics(Reference temperature 30℃)

Item Curves Test current ln(A) Status Time limit for tripping or non-tripping Expected result Remarks
a B、C、D 1.13ln Cold

t≤1h(In≤63A)

t≤2h(In>63A)

Non-tripping Current smoothly rises to specified value within 5s
b B、C、D 1.45ln Following item a test

t<1h(In≤63A)

t<2h(In>63A)

Tripping
c B、C、D 2.55ln Cold 1s<t<60s(ln≤32A)
1s<t<120s(ln>32A)
Tripping
d B
C
D
3ln
5ln
10ln
Cold t≤0.1s Non-tripping Switch on the power supply by closing the auxiliary switch
e B
C
D
5ln
10ln
20ln
Cold t<0.1s Tripping Switch on the power supply by closing the auxiliary switch

Note: The term “cold ” means that the test is carried out at a reference calibration temperature without load before the test.

4 Nominal operation conditions
4.1 : Ambient temp. range:-5℃~+40 ℃,average temperature in 24 hours not exceed +35℃
4.2 : Altitude:≤ 2000m;
4.3 : At mounting site, relative humidity not exceed 50% at the max temperature of +40 ℃,higher relative humidity is allowable under lower temperature, for example ,RH could be 90% at +20 ℃
4.4 : Mounting type : Din rail embedded(TH35-7.5)
4.5 Installation conditions
Any direction of the outer magnetic field of the installation site should not exceed 5 times than earth’s magnetic field; residual current operated circuit breaker should be mounted vertically, all places inclination no more than 5 °,power position above the handle , the installation place should be no significant impact and vibration.
4.6 Installation should be free from obvious shock and vibration.

5 Conductor requirements and cross-sectional area

Nominal cross-sectional area (mm2) Rated current In(A)
10 32<In≤50
16 50<In≤63
25 63<In≤80
35 80<In≤100
50 100<In≤125

6 Dimensions (unit :mm)

7 Tripping curve

8.CCC