Notice: Undefined index: HTTP_REFERER in /home/merhxrnc/showroom.merhein.com/wp-content/themes/merhein/single-product.php on line 10
EKL4 Short Circuit and Earth Fault Indicator Tester - Merhein Showroom

EKL4 Short Circuit and Earth Fault Indicator Tester

Inquire Now

Description

The EKL4 Short Circuit and Earth Fault Indicator Tester is an advanced monitoring device designed for electricity distribution networks, specifically for installation on RMU, cable branch boxes, and substations. This comprehensive unit provides real-time monitoring of short circuits and single-phase ground faults, effectively identifying the fault section in the corresponding cable. When a circuit breakdown occurs, the device promptly alerts staff, enabling rapid fault location and resolution. Its robust design not only enhances operational efficiency but also minimizes blackout duration, optimizing service delivery and economic benefits.

Main Functions:

  • Short Circuit Alarm: Measures current, triggering alarms when thresholds are exceeded, and communicates alerts to a central indicator.
  • Earth Fault Alarm: Monitors zero sequence current, alerting operators to ground faults.
  • Low Voltage Alert: Uses battery power to signal when voltage drops below normal levels.
  • Automatic Reset: Resets the device after a designated time unless manually overridden.
  • Manual Reset: Operators can acknowledge alerts by pressing a reset button for three seconds.
  • Remote Automation: Capable of receiving reset signals and transmitting alarm alerts remotely.
  • Self-Test Capability: The device can conduct self-diagnostic tests to ensure functionality.

Specifications

Parameter Details
Short Circuit Current Alarm ≥150A (continuously adjustable), factory setting 1200A, time delay adjustable from 20-300ms (factory setting 60ms)
Earth Circuit Current Alarm 5A-400A (continuously adjustable), factory setting 10A, time delay adjustable from 20-300ms (factory setting 200ms)
Working Power ER14505 lithium battery 3.6V/1.9Ah (valid for up to 8 years)
Standby Current ≤5μA
Automatic Reset Time 1 second to 32 hours (factory setting 8 hours)
Indicator Protection Grade Mainframe IP40, Sensor IP65
Relay Specifications 30DC/2A; 230VAC/1A
Short Circuit Current Sensor Withstands current of 20kA for 4 seconds
Operating Environment -40℃ to +75℃; Relative Humidity ≤95%
Usage Range In systems below 20kV

Additional Information

Device List:

No. Components
1 Mainframe: 1 set
2 Short Circuit Sensor: 3 pcs
3 Earthing Sensor: 1 pc
4 Short Circuit Transmission Fiber: 3 pcs (standard length: 2m each), Earthing Transmission Wire: 1 pc (standard length: 2m)
5 Certificate of Approval
6 Installation Instructions

Product Inquiry Form