The MV Station Integrated Outdoor Inverter is a robust and reliable solution designed for efficient energy conversion in various environments. This innovative system combines an inverter, transformer, and communication & monitoring system into a single unit, ensuring seamless operation and integration. With a significant 1500V large capacity for centralized grid connection, it provides a cost-effective energy solution with minimal initial investment. Engineered to withstand harsh conditions, this inverter adapts effortlessly to high temperatures, humidity, dust, and salt spray, guaranteeing durability and performance in challenging settings.
Specifications
Parameter | Details |
---|---|
Max. PV input voltage | 1500V |
Max. input current | 3260A*2 |
MPP voltage range for nominal power | 900~1300V |
Number of MPPT trackers | 2 |
Number of DC inputs | (14~20)*2 |
Rated AC output power | 2*2500kVA@50℃ |
Max. AC output power | 2*2875kVA@25℃ |
AC voltage range | 20~35kV |
Rated grid frequency/range | 50 Hz/ 45~55 Hz, 60Hz/ 55~65 Hz |
Output current harmonic (at nominal power) | < 3 % |
DC current injection | < 0.5% In |
Power factor at nominal power/range | >0.99/ 0.8 lagging to 0.8 leading |
Weight | 25t |
Protection level | Inverter: IP65, Others: IP54 |
Temperature | -30~+60℃ (>50℃ derating) |
Allowed humidity (non-condensing) | 0 – 95 % |
Cooling mode | Temperature controlled forced air cooling |
Max. operating altitude | 2000m (standard) / > 2000m (optional) |
Display | LCD |
Communication port | RS485/Ethernet |
Additional Information
- DC input protection: Load break switch + fuse
- AC output protection: Circuit breaker
- Overvoltage protection: DC Type II / AC Type II
- Leakage current monitoring: Yes
- Grid monitoring/Ground fault monitoring: Yes/Yes
- Insulation monitoring: Yes
- Overheat protection: Yes
- Night SVG function: Optional
- Anti-PID function: Optional