High Frequency Online LCD Display Transformerless UPS Power Supply for 1-20kVA

Inquire Now

High frequency W1KVA-20KVA series is based on double conversion on-line intelligent UPS, it adopts advanced DSP digital control technology, has functions of higher output performance indicators and a number of innovative design features, is the ideal solution for small-capacity power supply scenarios, can fully eliminate all kinds of power grid problem. Support for tower installation, built-in battery.

W1KVA-20KVA

Main feature

1.Full digital control technology

2.Output power factor up to 1.0

3.LCD display panel

4.RS232 communication port

5.Intelligent SNMP+USB+EPO+dry contact (optional)

6.High power density design

7.AC/AC efficiency up to 95%

8.ECO function

Application

1.Data center

2.Network device

3.Commercial facility

4.Precision instrument

5.Home, Office and other AC power supply


Specification


Model

W1KS(L)

W2KS(L)

W3KS(L)

W6KS(L)

W/3W10KS(L)

W/3W15KL

W/3W20KL

Capacity

1kVA

2kVA

3kVA

6kVA

10kVA

15kVA

20kVA

Input features

Voltage(Vac)

120VAC300VAC

120-288(1/1)/266-475(3 /1)

Frequency(HZ)

4566

Phase

Single phase

Single phase/3φ4W+PE

Power Factor

Full load ≥0.95

Full load ≥0.98

Battery voltage(Vdc

24/36

72/72

72/96

192

Battery type

2*7Ah 12V/External

6*7Ah 12V/External

6*7Ah 12V/External

16*7Ah 12V/External

Externa

Output features

Power factor

1.0

0.9/1.0

Voltage(V)

220/230/240±1%

Frequency(HZ)

50/60±0.05%battery mode)

Transfer Time(ms

0

92%

93%

Waveform

Sine Wave,Linear Load THD<3%Non-linear Load THD<5%

Overload

105%~129% full load keep 60s;130%~150% load keep 30s;

Above 150% load keep 300ms

Crest Factor

>3:1

Output socket

EU/IEC/UK( optional)

Terminal block

Others

DC start

Yes

Backup time

Normally 5-8 mins/Long time need to depend on demands

Communication function

RS232(USB/dry contact are optional)

SNMPoptional)

Can be network monitored by SNMP adapter

Display

LED display UPS work status, LCD display UPS work parameters

Noise (dB)

<50(within 1 meter)

<55(within 1 meter)

Parallel function

No

Yes(optional)

Alarm

Battery low-voltage, mains abnormal, overload, UPS fault, over temperature protection

Protection

Input over-voltage protection, battery undervoltage protection, overload protection, short circuit protection, over temperature protection

Working temperature(

040

Humidity

095%Non condensing

Size(D×W×H) (mm)

355*145*226

402*190*326

500*248*616(S &3/1)/500*240*460(L)

500*248*616

Weight(KG)

12/10

26/19

27/20

52/21

58/25(1/1 )

64/30(3/1)

36

39

Note

“L” is long backup UPS“S” is standard UPS

Because the products are continuously improved, please contact the company or dealer to inquiry the latest specification.