HVD-Q-2 LED Display Live Line Switchgear Indicator For High Voltage
Inquire NowThe HVD-Q-2 LED Display Live Line Switchgear Indicator is an advanced non-contact high-voltage live detection device designed to enhance safety in power systems. Utilizing an integrated three-phase continuous display, this innovative instrument accurately tests voltage loss in medium-voltage switchgear without direct connection to high-voltage live components. It senses electric field signals, reflecting the charging status of high-voltage equipment with a reliable locking function.
Compliant with IEC 61243-5 and IEC 62271-213 standards, the HVD-Q-2 is ideal for indoor high-voltage electrical equipment, preventing accidental access to live areas and electrical misoperations. Key features include flashing display alerts, sound alarms, self-check capabilities, and a forced locking circuit that works in conjunction with electromagnetic locks and microcomputer anti-misoperation functions. The device is widely applicable in 7.2kV to 40.5kV electrical equipment, ensuring safety during operations like grounding switch management.
Features
- Fail-safe voltage testing and protection
- Integrated self-test function with a self-test button
- High voltage and disconnection alarms
- Visual indication via bright LED or LCD screen
- Maintenance-free operation without batteries or auxiliary voltage
- Fully self-monitoring system
- Three-phase live voltage indication
- Electromagnetic lock for automatic locking
- Relay signal output for interlocking indication
- Phase sequence detection point
Attribute | Details |
---|---|
Rated voltage | 24V/110V/220V |
Voltage level | 1.52 kV (Medium-voltage) |
Contact capacity (Passive) | 8A, 250VAC/48VDC |
Power consumption | <2W |
Working frequency | 50Hz/60Hz |
Standard | IEC 61243-5, IEC 62271-213 |
Insulation strength | 2kV, 1min |
Nominal Voltage | 3-3.6kV, 6-7.2kV, 10-12kV, 20-24kV, 35-40.5kV |
Shielded Cable Length | 2M, or customized |
Operating temperature | -25°C to 55°C |
Storage temperature | -30°C to 75°C |
Protection class | IP40/IP65 |
Type of interface | LRM |
Lifetime | Minimum 31 years (MTBF) |
Mounting Dimension (WxHxD) | Panel window size 92x45mm; Recommended depth 130mm |