KNLE2-63 Earth leakage circuit breaker

Inquire Now

Description

KNLE2-63 Earth Leakage Circuit Breaker is designed for effective leakage protection in single-phase AC circuits at 50/60Hz with a rated voltage of 240V and a maximum current of 63A. This advanced circuit breaker automatically disconnects power within 0.1 seconds in the event of a human electric shock or excessive leakage current, ensuring safety and preventing accidents caused by current leakage. It also protects against overload and short circuits, making it ideal for various applications where reliable electrical protection is essential. The KNLE2-63 complies with IEC/EN61009-1 and GB16917.1 standards, ensuring high safety and performance standards.

Specifications

Attribute Details
Frame Class 63 A
Rated Working Voltage 240V
Rated Frequency 50/60Hz
Rated Working Current 6, 10, 16, 20, 25, 32, 40, 50, 63 A
Rated Residual Operating Current 0.01, 0.03 A
Rated Residual Un-Operating Current 0.005, 0.015 A
Sensitivity C Type
Maximum Operating Time I△n ≤ 0.3s, 5I△n ≤ 0.04s
Instant Release Type B, C, D
Rated Limiting Short-Circuit Current 6000 A
Limiting Value of Un-Operating Current 6In
Poles 1P+N
Mechanical Life 8000
Electric Life 4000

Additional Information

Sequence NO. Release Test Current I/In Start State Tripping Time Expected Result
1 C 1.13In Cold state t ≤ 1h Not tripping
2 C 1.45In Start after test 1 t < 1h Tripping
3 C 2.55In Cold state 1s < t < 60s Tripping
4 C 5In Cold state t ≤ 0.1s Not tripping
5 C 10In Cold state t < 0.1s Tripping

1

Product Inquiry Form

Thanks your message successfully submitted.