Polymer insulator

Inquire Now

Polymer insulator

Composite tension & suspension insulator mainly consists of a core rod (ECR type or FRP type), silicone rubber housing and metal end fittings.

Material of end fittings: #45 forged steel, hot dip galvanized,thickness of the galvanization: ≥86μm

Material of the core: Epoxy & glass fiber (ECR type or FRP type).

Material of the weather sheds: HTV silicone, color grey

Housing to core: They are chemically bonded and the interface strength between the housing and core is higher than the tearing strength of housing itself.

Sealing: Juncture between end fitting and core rod is totally embedded in HTV silicone rubber, eliminating conventional and traditional sealing defects: (The other type is available that use RTV silicone sealant to seal the juncture between end fitting and core rod).

IEC61109

Item No. Dimensions Mechanical Electrical
Height(mm) Min Dry Arcing Distance(mm) Min Creepage Distance(mm) Diameter of the rod(mm) Number of sheds Specified Mechanical Load(SML) (kN) Routine Test Load(RTL) (kN) Rated Voltage kV Critical Impulse Flashover Voltage
(Pos/Neg) kV
Power Frequency Flashover Voltage
(Dry/Wet) kV
FXB 11-15kV 335 200 460 17 4 70 35 11-15 140/145 70/60
FXB 24-27kV 460 235 675 17 6 70 35 24-27 170/190 75/65
FXB 33-36kV 545 350 900 17 8 70 35 33-36 230/250 105/95
FXB 33-36kV 440 360 900 18 9 40 20 33-36 230/250 95/85
FXB 33-36kV 440 360 900 18 9 70 35 33-36 230/250 95/85
FXB 69kV 970±10 780 2130 18 18 100 50 69 410 200/185
FXB 132kV 1475±15 1300 3850 18 30 100 50 132 550 275/235
FXB 230kV 2380±30 1900 6000 24 60 160 80 230 1315 780/700